Leave Your Message
AI Helps Write
Din-Rail DC Single Phase Energy Meter SPM90 with basic function and pulse output, optional Shunt, Modbus protocol
Din-rail type DC energy meter

Din-Rail DC Single Phase Energy Meter SPM90 with basic function and pulse output, optional Shunt, Modbus protocol


1.Real-time measure one circuit DC voltage, current, power , kWh

2.High accuracy: Class 0.5

3.One LED indicate pulse output

4.RS485 port, MODBUS-RTU or DL/T645 protocol (optional)

5.35mm DIN rail installing, standard DIN ED5002

6.Shunt: 100A, 200A, 300A, 400A

      Main Documents

      Compatible Software

      PiEMS System1vwd

      Smart PiEMS System

      Product Introduction

      SPM90 single phase dc energy meter parameters
      • SPM90 offers a cost-attractive, competitive range of single-phase DIN rail-mounted energy meters ideal for DC panel, charging pile and telecom base stations applications. Combined with RS485 port, Modbus-RTU or DL/T 645-2007 communication protocol, it makes easy to integrate electrical distribution measurements into Smart PiEMS energy management system and Smart PiDMS distribution management system.
      SPM90 din rail 35mm
        This meter series can measure voltage, current, power and active energy in DC system. Not only can it be used as local display, but it can also be used in measuring system by connecting with industrial control equipment and computers. It is a high-performance automation meter that can work with modern DC power distribution system in industrial and mining industry, civil building and building automation.

        Product performance fully meets the according technical requirements of GB/T 29318-2012 (Energy measurement of non-vehicle charger of Electromotive) and Class 0.5 of DL/T 1484-2015 (Technical Regulations of DC energy power).

      Specification

      Parameter

      Range

      Rated working voltage

      DC24V (9-72VDC)

      Rated Parameter

      Rated current

      Can be set:

      50A,100A,150A,200A,300A,400A,500A,600A,800A,etc(The maximum measurement value is 2000A),use external 75mV Current Shunt input

       

      Rated voltage

      1000VDC,and allows for long-term overload of 1.5 times (up to 1500VDC)

      Parameter

      Accuracy

      Voltage

      0.2%

       

      Current

      0.2%

      Electrical Parameter Accuracy

      Energy

      0.5S

       

      Power

      0.5%

       

      Parameter

      Performance

       

      Consumption

      ≤ 1W

      Normal working temperature

      -10℃ ~ +55℃

      Environment Temperature

      Extreme working temperature

      -25℃ ~ +70℃

       

      Storage temperature

      -25℃ ~ +70℃

       

      Working humidity

      Under 95%

      Insulation performance

      Power-frequency

      withstand voltage

      4400VAC

       

      Insulation resistance

      ≥100MΩ

       

      Impulse voltage

      6000V

      IP Protection grade

      Complete machine

      IP20

       

      Item

      Reference standard

      Experiment grade

      Electrostatic Discharge

      GB/T17626.2-2018

      Grade 4

       

      Radiated immunity of radiofrequency electromagnetic fields

      GB/T17626.3-2016

      Grade 3

       

      Electrical fast transient burst immunity

      GB/T17626.4-2018

      Grade 4

      Electromagnetic compatibility

      Surge (impact) immunity

      GB/T17626.5-2019

      Grade 4

       

      Conduction noise immunity of radio-frequency field induction

      GB/T17626.6-2017

      Grade 3

       

      Electromagnetic emission limiting value

      GB 4824-2019 (CISPR11:2016)

      Grade B

       

      Voltage sag,shot-time interruption immunity

      GB/T17626.11-2008

      Conformed

      Note:The accuracy of electrical parameters is met within the normal operating temperature range.